In high sand and dust prone areas such as deserts and Gobi, the anti-corrosion ability of Vacuum switchgear directly determines the lifespan of photovoltaic power plants.
1、 Core threat of sand and dust corrosion
Mechanical wear: Quartz sand (Mohs hardness 7) wears down the paint layer of the cabinet, accelerating metal corrosion.
Electrochemical corrosion: Salt (NaCl content>3%) in sand and dust forms an electrolyte in a humid environment, causing pitting corrosion of the cabinet.Insulation failure: Dust accumulation causes creepage inside the cabinet (>5mm dust accumulation can cause 12kV equipment to flashover).
Implementation caseA 200MW photovoltaic power station in Dunhuang (with an average of over 120 days of sandstorms per year)
Problem: After 2 years of operation, the fault rate of circuit breaker mechanism jamming in traditional switchgear exceeds 30%.
Solution:Replace with customized sand proof vacuum switchgear (KYN28-12Z)
Key parameters:Protection level: IP6X (dustproof)+IPX5 (waterproof) Sealing pressure: 80Pa (positive pressure inside the cabinet) Surface treatment: Arc sprayed aluminum+RTV coatingeffect:3 years of zero institutional jamming failure 60% reduction in maintenance costs (compared to the original equipment)
Oil&Gas exploited
Automotive Manufacturing
Transportation & Dlistrlbutlon
Manufacture
Industrial Construction
Green Energy
Copyright ? 2024 All Rights Reserved
Back to top
Comment
(0)